Suppression and Control of Class C Cargo Compartments Fires
-
1985-02-01
-
By Blake, David
Details
-
Creators:
-
Corporate Creators:
-
Subject/TRT Terms:
-
Publication/ Report Number:
-
Resource Type:
-
Geographical Coverage:
-
Edition:Final Report
-
Corporate Publisher:
-
Abstract:A total of 23 fire tests were conducted in a 2357-cubic foot simulated class C cargo compartment. Various lining materials, fire sources, loading configurations, and smoke detectors were used to determine the ability of class C cargo compartments to control fires. The simulated class C cargo compartment did not successfully control the test fires in all cases. The major conclusion of this study is that the 45 degrees bunsen burner test specified in FAR 25.855 does not assure that cargo liners will not burn through when subjected to realistic fires. Keywords Class C, Halon 1301, and Burn-through.
-