Live load testing and load rating of five reinforced concrete bridges.

Filetype[PDF-11.72 MB]


Select the Download button to view the document
This document is over 5mb in size and cannot be previewed
English

Details:

  • Creators:
  • Corporate Creators:
  • Subject/TRT Terms:
  • Publication/ Report Number:
  • Resource Type:
  • Geographical Coverage:
  • Corporate Publisher:
  • Abstract:
    Five cast-in-place concrete T-beam bridges – Eustis #5341, Whitefield #3831, Cambridge #3291, Eddington #5107,

    and Albion #2832 – were live load tested. Revised load ratings were computed either using test data or detailed

    analysis when possible. In four of the five bridges, increases in rating factors were made through analysis alone. The

    Cambridge bridge was shown to have HL-93 operating rating factors greater than 1.0 for both shear and moment

    without testing. Additionally, gains are presented for two of the five bridges (Eustis and Whitefield) where test

    data was used to compute an adjustment factor K for midspan bending, where the revised rating factor equals K x

    RF. Adjustment factors were found to be 1.61 and 1.24 for Eustis and Whitefield, increasing their flexural rating

    factors to 1.14 and 1.06 if accepted by the Maine DOT. Similarly, our analyses indicate that Eustis has a rating

    capacity greater than 1.0 for shear. While Whitefield has a rating factor greater than 1.0 for shear at the supports, the

    rating factor for shear near the termination of the bent-up reinforcing is 0.48 based on our analyses.

    Low loads used in the live load tests of both Albion and Eddington, where only one truck was provided on site,

    preclude the development of revised rating factors based on the test data. However, both of these structures did

    exhibit better-than-expected live load distribution. Further, analysis of the Albion bridge indicates that the

    consultant-provided load ratings for this structure can likely be increased significantly.

    Use of these revised load ratings, live load test data, and extrapolation of these results to other structures is at the

    sole discretion of the bridge owner.

    The objective of this study, to implement an effective live load testing bridge program, was fulfilled